Technical Data - ABB ACH580 Series User Manual

E-clipse bypass and packaged drive
Table of Contents

Advertisement

ACH580 E-Clipse bypass and packaged drive user manual

Technical data

Vertical enclosure terminals maximum wire size and terminal torque values
ACH580-VxR-04A6-2
ACH580-VxR-06A6-2
ACH580-VxR-07A5-2
ACH580-VxR-10A6-2
ACH580-VxR-017A-2
ACH580-VxR-024A-2
ACH580-VxR-031A-2
ACH580-VxR-046A-2
ACH580-VxR-059A-2
ACH580-VxR-075A-2
1) "VxR" represents both VCR and VDR.
ACH580-VxR-02A1-4
ACH580-VxR-03A0-4
ACH580-VxR-03A5-4
ACH580-VxR-04A8-4
ACH580-VxR-07A6-4
ACH580-VxR-012A-4
ACH580-VxR-014A-4
ACH580-VxR-023A-4
ACH580-VxR-027A-4
ACH580-VxR-034A-4
ACH580-VxR-044A-4
ACH580-VxR-052A-4
ACH580-VxR-065A-4
ACH580-VxR-077A-4
1) "VxR" represents both VCR and VDR.
Nominal Output
Ratings
1
Type Code
Drive
Current
A
4.6
6.6
7.5
10.6
16.7
24.2
30.8
46.2
59.4
74.8
Nominal Output
Ratings
1
Type Code
Drive
Current
A
2.1
3.0
3.5
4.8
7.6
12
14
23
27
34
44
52
65
77
Maximum Wire Size and Terminal Torque
Frame
Package
Size
Circuit
Power
Breaker
HP
208/230 Volts
1
R1
1.5
R1
#10
62 in-lbs
2
R1
3
R1
5
R1
7.5
R2
#8
62 in-lbs
10
R2
15
R3
#2
20
R3
62 in-lbs
25
R4
Maximum Wire Size and Terminal Torque
Frame
Package
Size
Circuit
Power
Breaker
HP
460 Volts
1
R1
1.5
R1
2
R1
#12
62 in-lbs
3
R1
5
R1
7.5
R1
10
R2
#10
62 in-lbs
15
R2
20
R3
#8
25
R3
62 in-lbs
30
R3
40
R4
#2
50
R4
62 in-lbs
60
R4
Disconnect
Motor
Switch
Termination
#10
55 in-lbs
#6
11-13 in-lbs
#6
55 in-lbs
#4
#1
55 in-lbs
35 in-lbs
#2
55 in-lbs
#1
#2/0
55 in-lbs
110 in-lbs
#1/0
75 in-lbs
Disconnect
Motor
Switch
Termination
#10
55 in-lbs
#6
11-13 in-lbs
#8
55 in-lbs
#6
55 in-lbs
#4
55 in-lbs
#1
35 in-lbs
#3
55 in-lbs
#2
55 in-lbs
#1
#2/0
55 in-lbs
110 in-lbs
#1/0
75 in-lbs
Technical data
201
Ground
Lugs
#4
35 in-lbs
#2
50 in-lbs
Ground
Lugs
#4
35 in-lbs
#2
50 in-lbs

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents