ABB ACH580 Series User Manual page 158

E-clipse bypass and packaged drive
Table of Contents

Advertisement

ACH580 E-Clipse bypass and packaged drive user manual
Bit
8
9
10
11
12
13
14
15
16
17
18
19
Bit
16...26
27
28
DCU Profile CONTROL WORD
Name
Value
STPMODE_EM
1
0
STPMODE_C
1
0
RAMP_2
1
0
RAMP_OUT_0
1
0
RAMP_HOLD
1
0
RAMP_IN_0
1
0
RREQ_LOCALLOC 1
0
TORQLIM2
1
0
FBLOCAL_CTL
1
0
FBLOCAL_REF
1
0
START_DISABLE1
1
0
START_DISABLE2
1
0
DCU Profile CONTROL WORD
Name
Value
REF_CONST
1
0
REF_AVE
1
0
Command/Req.
Emergency ramp
stop mode
(no op)
Coast stop mode
(no op)
Ramp pair 2
Ramp pair 1
Ramp output to 0
(no op)
Ramp freeze
(no op)
Ramp input to 0
(no op)
Local mode lock
In lock, drive will not switch to local
mode.
(no op)
Torque limit pair 2
Torque limit pair 1
FB Local mode for
Field bus sets these bits-> drive moves
control word
to field bus local control mode of
requested.
control word or reference (field bus
steals the control)
FB Local mode for
control word
requested.
FB Local mode for
control word
requested.
FB Local mode for
control word
requested.
Start disabled 1
Inverted Start Interlock x2. When Start
Interlock is missing, the drive doesn't
Start enabled 1 on
set STARTED status bit.
Start disabled 2
Start enabled 2 on
Function
Reserved
Constant speed ref. These bits are only for supervision
purposes.
(no op)
Average speed ref.
(no op)
149
Comments
Comments