10 PLC CPU Initial Setup

10.1.3 Setting Multi-CPU Parameters

(1) Double click [Module Configuration] from the project of the navigation window to display the unit configuration
drawing dialog.
(2) Select [On line]-[Read Module Configuration from PLC] from the menu.
The module configuration diagram appears, which is configured with the same components (objects) as the actual
system.
(3) Double click [Parameter]-[R04CPU]-[CPU Parameter] in the navigation window and select "Yes" in the displayed
dialog box.