C80 Series Connection and Setup Manual
19 Appx.2: EMC Installation Guidelines
19.5.2 Shield Treatment of Cables
Use shielded cables for the cables wired outside the panel.
Use a shield clamp within 10cm of the lead-out port from the panel. (Refer to "EMC Countermeasure Parts: Shield Clamp
Fitting".)
(1) Ethernet cable [J303 cable]
GOT
- Use a shielded cable. Use a shield clamp within 10cm from the panel's inlet/outlet.
- When using a ferrite core, install it on both ends of the connected units.
(Note) If the wiring is routed in the panel, no ferrite core is required.
IB-1501452-C
Shield clamp
R16NCCPU
J303 cable
Ferrite core