Parameters
7.6.6
Basic-stage heating parameter window
This window is only visible if the Deactivated option has not been selected in the Basic-stage heating
parameter in the Application parameters parameter window.
In actuator mode, this window is deactivated and hidden.
The basic-stage heating of the temperature controller is parameterized in this window. The settings for the
control type, limitation of the control range, the behavior on sending the control value and the limit
temperature are made.
Fig. 13: Basic-stage heating parameter window
7.6.6.1
Basic-stage heating control value type
Options:
This parameter is used to specify the control and control value type for the basic-stage heating.
The standard value for the parameter is dependent on the selection in the Basic-stage heating and
Actuate basic-stage heating via parameters (Application parameters parameter window).
On the selection of the physical device output for the actuation of the basic-stage heating or on output via
KNX group object, the controller has a fixed pre-configuration that cannot be changed. The pre-configured
controller type is dependent here on the option selected in the Basic-stage heating parameter.
The only exception is on the selection of Free configuration. In this situation, everything can be selected
and set freely.
2-point 1 bit (On/Off)
2-point 1 byte (0/100%)
PI continuous (0...100 %)
PI PWM (On/Off)
VC/S 4.x.1 | 2CDC508220D0211 Rev. A 73