KNX
Parameters
If the input state changes during the block phase, the new group object value is sent immediately after the
block is released. If the input state remains the same during the block phase, the group object value is not
sent. The minimum signal duration does not start until the Block has finished.
Block is deactivated after an ETS reset, a bus voltage recovery or a download.
7.11.1.5.4
Dependent parameter
Reaction on event X
The following apply to the Reaction on event 0 and Reaction on event 1 parameters.
Options:
The standard value for Reaction on event 1 is On. The standard value for Reaction on event 0 is Off.
This determines how the group object reacts. If the Distinction between long and short operation
parameter is set to Yes, the reaction occurs with a short or long operation. If it is set to No, it occurs with
each edge change.
If it is set to End cyclic transmission, it is important to note that this is only effective if the Send status
value parameter is set to After a change and cyclically.
No edge evaluation
On
Off
Toggle
End cyclic transmission
Note
VC/S 4.x.1 | 2CDC508220D0211 Rev. A 193