ABB i-bus KNX Product Manual page 116

Vc/s 4.x.1 valve drive controller
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

®
ABB i-bus
KNX
Parameters
7.6.9.1.1
2-point 1 bit (On/Off), 2-point 1 byte (0/100 %)
The following parameters are enabled if the 2-point 1 bit (On/Off) or 2-point 1 byte (0/100%) option has
been selected in the Additional-stage cooling control value type parameter.
7.6.9.1.1.1
Dependent parameter
Temperature difference from basic-stage cooling
Options:
The temperature difference from basic-stage cooling specifies the value from which or up to which
the additional-stage cooling is to be active. If the actual temperature is below the setpoint temperature by
the value selected here, the additional stage is active.
This action occurs both if the actual temperature drops below the threshold and if it is already below
the threshold.
Example 1:
Temperature difference from basic-stage cooling: 2 K
Setpoint temperature: 23 °C
Actual temperature: 27 °C
Additional stage is active until the actual temperature reaches 25 °C.
Example 2:
Temperature difference from basic-stage cooling: 2 K
Setpoint temperature: 23 °C
Actual temperature: 24 °C
Additional stage is inactive as long as the actual temperature is above 25 °C.
114 2CDC508220D0211 Rev. A | VC/S 4.x.1
00.0...02.0...25.5 K

Advertisement

Table of Contents
loading

Table of Contents