KNX
Parameters
7.7.4.2.3
Dependent parameter
Increase for Standby cooling
This parameter is only visible if the device has been parameterized for cooling and the Deactivated option
has not been selected for the Basic-stage cooling parameter in the Application parameters parameter
window, and the No option has been selected for the Comfort heating setpoint = Comfort cooling setpoint
parameter.
Options:
This value defines the setpoint for the comfort cooling temperature. If the device is the type of operation
cooling and is changed to the Comfort operating mode, the device regulates to this temperature.
The controller does not change the type of operation to reach this temperature, instead it ensures this
temperature is not exceeded on an increase in the actual temperature.
7.7.4.2.4
Dependent parameter
Increase for Economy cooling
This parameter is only visible if the device has been parameterized for cooling and the Deactivated option
has not been selected for the Basic-stage cooling parameter in the Application parameters parameter
window, and the Setpoint specification and adjustment parameter has been parameterized with the
Relative option.
Options:
This parameter is used to set the temperature that is to apply in the Economy operating mode in the type
of operation cooling. This is defined here as the increase in relation to the comfort cooling setpoint.
The controller does not change the type of operation to reach this temperature, instead it ensures this
temperature is not exceeded on an increase in the actual temperature.
136 2CDC508220D0211 Rev. A | VC/S 4.x.1
0...2...15 K
Note
0...4...15 K
Note