Basic-stage cooling parameter window

This window is only visible if the Deactivated option has not been selected in the Basic-stage cooling
parameter in the Application parameters parameter window.
In actuator mode, this window is deactivated and hidden.
The basic-stage cooling of the temperature controller is parameterized in this window. The settings for the
control type, limitation of the control range, the behavior on sending the control value and the limit
temperature are made.
Fig. 15: Basic-stage cooling parameter window
7.6.8.1

Basic-stage cooling control value type

Options:
This parameter is used to specify the control and control value type for the basic-stage cooling.
The standard value for the parameter is dependent on the selection in the Basic-stage cooling and Actuate
basic-stage cooling via parameters (Application parameters parameter window).
On the selection of the physical device output for the actuation of the basic-stage cooling, the controller
has a fixed pre-configuration that cannot be changed. The pre-configured controller type is dependent here
on the option selected in the Basic-stage cooling parameter.
The only exception is on the selection of Free configuration. In this situation, everything can be selected
and set freely.
2-point 1 bit (On/Off)
2-point 1 byte (0/100%)
PI continuous (0...100 %)
PI PWM (On/Off)