8.3
Group objects Channel A – General
No.
10
This group object is enabled if the parameter Use forced operation is set to Forced operation 2 bit in the Monitoring
and safety parameter window.
This group object activates and deactivates forced operation.
Telegram value
(Bit 1 | Bit 0: Status of forced operation):
0 | 0: Forced operation inactive
0 | 1: Forced operation inactive
1 | 0: Forced operation active, forced OFF
1 | 0: Forced operation active, forced ON
11
The group object is enabled if the parameter Use forced operation is set to Forced operation 1 bit; 0 active or Forced operation
1 bit; 1 active in the Monitoring and safety parameter window.
This group object activates and deactivates forced operation.
Depending on the selected option, forced operation is activated with a 1 or 0 and deactivated with a 0 or 1.
12
This group object is enabled if the parameter Monitor receipt of heating/cooling changeover group object is set to Activated
in the Monitoring and safety parameter window.
This group object changes to the value 1 if the parametrized monitoring time was exceeded without a value being received on
the group object.
The status changes back to 0 when the group object is received again.
The group object is sent on each state change (0 > 1 or 1 > 0).
13
This group object is enabled if the parameter Monitor receipt of group object "Window contact" is set to Activated
in the Monitoring and safety parameter window.
This group object changes to the value 1 if the parametrized monitoring time was exceeded without the group object
being received.
The status changes back to 0 when the group object is received again.
The group object is sent on each state change (0 > 1 or 1 > 0).
200 2CDC508220D0211 Rev. A | VC/S 4.x.1
Object function
Forced operation 2 bit
Forced operation 1 bit
Error: heating/cooling receipt
Error: window contact receipt
Name
Channel A – General
Channel A – General
Channel A – General
Channel A – General
Data type
Flags
2 bit
C, W
DPT 2.001
1 bit
C, W
DPT 1.002
1 bit
C, R, T
DPT 1.002
1 bit
C, R, T
DPT 1.002