Summer Compensation - ABB i-bus KNX Product Manual

Vc/s 4.x.1 valve drive controller
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

®
ABB i-bus
KNX
Parameters
7.7.7.1
Dependent parameter
Send current setpoint cyclically
This parameter is only visible if the After a change and cyclically option has been selected in the
Send current setpoint parameter.
Options:
The cycle time with which the current setpoint is to be sent is specified here.
7.7.8

Summer compensation

This parameter is only visible if the device has been parameterized for cooling and the Deactivated option
has not been selected for the Basic-stage cooling parameter in the Application parameters parameter
window.
Options:
The summer compensation in the device can be activated using this parameter. The summer
compensation is used to obtain energy savings by increasing the setpoint depending on the outside
temperature to prevent large temperature differences between room and outside temperature and
the related risk of a heat shock.
Information about the function of the summer compensation, explanation of the function of the summer
compensation
no: The summer compensation is deactivated
yes: The summer compensation is activated. The dependent group objects Outside temperature for
summer compensation and Summer compensation active/inactive are displayed. The dependent
parameters (Lower) starting temperature for summer compensation, Setpoint temperature offset when
summer compensation starts, (Upper) escape temperature for summer compensation and Setpoint
temperature offset when summer compensation ends are displayed.
140 2CDC508220D0211 Rev. A | VC/S 4.x.1
5...240 min
No
Yes
Note

Advertisement

Table of Contents
loading

Table of Contents