ABB i-bus KNX Product Manual page 151

Vc/s 4.x.1 valve drive controller
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

®
ABB i-bus
KNX
Parameters
7.8.2.1.3.1
Dependent parameter
Time interval for cyclical monitoring
Options:
The monitoring time within which the group object must be received is specified using this parameter.
Otherwise the Error: heating/cooling receipt alarm object is changed to alarm and the value set in the
Heating/cooling mode when monitoring time exceeded parameter applies.
7.8.2.1.3.2
Dependent parameter
Heating/cooling mode when monitoring time exceeded
Options:
The selection made here defines which type of operation is to apply on the erroneous reception of the
Heating/cooling changeover group object. This type of operation remains active until a new value is
received in the group object monitored. If the Unchanged option is selected, the current type of operation
remains active.
00:00:30...00:05:00...18:12:15 hh:mm:ss
Unchanged
Heating
Cooling
VC/S 4.x.1 | 2CDC508220D0211 Rev. A 149