Vc/s 4.x.1 valve drive controller
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

®
ABB i-bus
KNX
Parameters
7.7.3.2

Yes

7.7.3.2.1
Dependent parameter
Hysteresis for Toggle heating/cooling
This parameter is only visible if the Yes option has been selected in the Comfort heating setpoint =
Comfort cooling setpoint parameter window.
Options:
The parameter defines the hysteresis for the changeover between heating and cooling. If the room
temperature exceeds the setpoint temperature plus hysteresis, the changeover is to cooling. If the room
temperature drops below the setpoint temperature minus hysteresis, the changeover is to heating.
A change between heating and cooling is only possible in the Comfort mode.
7.7.3.2.2
Dependent parameter
Comfort heating and cooling setpoint
This parameter is only visible if the Yes option has been selected in the Comfort heating setpoint =
Comfort cooling setpoint parameter window.
Options:
This value defines the setpoint for the comfort temperature for heating and cooling. If the operating mode
is changed to Comfort, the device regulates to this temperature in both types of operation heating and
cooling.
0.05...02.0...10.0 K
Note
10...21...40 °C
VC/S 4.x.1 | 2CDC508220D0211 Rev. A 131