ABB i-bus
KNX
Parameters
7.10.1.1.3
Dependent parameter
Max. manual increase in cooling mode via KNX
This parameter is only displayed if you select No when setting Connect analog room control unit to
physical device input a.
Options:
The parameter determines the maximum setpoint increase that can be manually set via KNX in Cooling
mode. Use the Request setpoint adjustment group object to increase the Comfort cooling setpoint by
a maximum of the value set here.
If the object receives a value that exceeds the value set here, the maximum possible increase is applied,
and the request confirmed with the adjusted value in the Confirm setpoint adjustment group object.
7.10.1.1.4
Dependent parameter
Max. manual reduction in cooling mode via KNX
This parameter is only displayed if you select No when setting Connect analog room control unit to
physical device input a.
Options:
The parameter determines the maximum setpoint increase that can be manually set via KNX in Cooling
mode. You can use the Request setpoint adjustment group object to reduce the Comfort cooling setpoint
by a maximum of the value set here.
If the object receives a value that exceeds the value set here, the maximum possible reduction is
applied, and the request confirmed with the adjusted value in the Confirm setpoint adjustment group
object.
0...3...9 K
Note
0...3...9 K
Note
VC/S 4.x.1 | 2CDC508220D0211 Rev. A 167