Mitsubishi Electric Melsec iQ-R Series User Manual page 92

Hart-enabled analog-digital converter module
Hide thumbs Also See for Melsec iQ-R Series:
Table of Contents

Advertisement

Operating condition setting completed flag
When changing values of the buffer memory, use 'Operating condition setting completed flag' (X9) as an interlock condition to
turn on and off 'Operating condition setting request' (Y9). For the buffer memory addresses that require turning on and off of
'Operating condition setting request' (Y9) to enable the new values, refer to the following.
Page 95 List of buffer memory addresses
When 'Operating condition setting completed flag' (X9) is off, the A/D conversion is not performed.
When 'Operating condition setting request' (Y9) is on, 'Operating condition setting completed flag' (X9) turns off.
'Module READY' (X0)
'Operating condition setting
completed flag' (X9)
'Operating condition setting
request' (Y9)
'A/D conversion completed flag'
(XE)
Performed by the A/D converter module
Performed by a program
■Device number
The following shows the device number of this input signal.
Signal name
Operating condition setting completed flag
APPX
90
Appendix 2 I/O Signals
ON
ON
OFF
ON
ON
OFF
CH1
X9
ON
OFF
ON
CH2
CH3
CH4
CH5
CH6
CH7
CH8