Constituent device
To use the HART communication function, an external device (HART-enabled device) that supports the HART communication
is required. The A/D converter module supports HART revision 7. For how to perform wiring for a HART-enabled device, refer
to the following.
MELSEC iQ-R HART-Enabled Analog-Digital Converter Module User's Manual (Startup)
Procedures of the HART communication function
The following describes the procedures to use the HART communication function.
1.
Wiring for the HART-enabled device
Perform wiring for the A/D converter module and the HART-enabled device. ( MELSEC iQ-R HART-Enabled Analog-
Digital Converter Module User's Manual (Startup))
2.
Settings using CommDTM and Device DTM
Set parameters of the HART-enabled device and communication path from CommDTM and Device DTM. (Page 59
CommDTM)
These settings are not required depending on the used HART-enabled device and control settings.
3.
Start of HART communication
Configure the settings of the HART communication function and start the HART communication. (Page 19 Start of HART
communication)
4.
Monitoring of HART device variables
Monitor HART device variables of the HART-enabled device from the A/D converter module. (Page 21 Monitoring of
HART device variables)
5.
Diagnostics of the HART-enabled device
Execute the diagnostics of the HART-enabled device. (Page 22 Diagnostics of the HART-enabled device)
6.
Execution of HART command
A HART command can be executed from the A/D converter module to the HART-enabled device at an arbitrary timing.
(Page 23 Execution of HART command)
Restrictions and precautions
The HART communication function has the following restrictions and precautions.
■Range switching function
When the HART communication function is used, the availability of the input range is not restricted. However, input a current
within the range of 4 to 20mA to a channel where the HART communication function is used. When a current outside the
range of 4 to 20mA is input, the HART communication may not be properly performed.
■A/D conversion enable/disable setting function
Unlike other functions, the HART communication function can be used even when the A/D conversion is disabled. However,
the digital output value and digital operation value are not updated for the channel on which A/D conversion is disabled. To
use the digital output value and digital operation value for the control in a channel where the HART communication function is
used, enable the A/D conversion.
1 FUNCTIONS
18
1.3 HART Communication Function