Setting method
1.
Set "Warning output function (Rate alarm)" to "Enable".
[Navigation window] [Parameter] [Module Information] Module model name [Application setting] [Warning
output function (Rate alarm)]
2.
Set a warning detection cycle of rate alarms.
Set the cycle in "Rate alarm detection cycle setting".
Item
Rate alarm detection cycle setting
3.
Set values for "Rate alarm upper limit value" and "Rate alarm lower limit value".
Set a value to the maximum value (32000) of the digital output value in increments of 0.1%.
Item
Rate alarm upper limit value
Rate alarm lower limit value
Set values within the range satisfying the condition "Rate alarm upper limit value > Rate alarm lower limit
value".
Setting range
1 to 32000 (times)
Setting range
-3276.8 to 3276.7 (%)
1 FUNCTIONS
1.8 Warning Output Function
1
39