Mitsubishi Electric Melsec iQ-R Series User Manual page 29

Hart-enabled analog-digital converter module
Hide thumbs Also See for Melsec iQ-R Series:
Table of Contents

Advertisement

Moving average
The A/D converter module averages digital output values taken at every sampling cycle for a specified number of times, and
stores a mean value in the buffer memory. Since the averaging processing is performed on a moving set of sampling, the
latest digital output values can be obtained.
The following figure shows the moving average processing of when the set number of times is five.
32000
16000
'CH1 Digital output value' (Un\G400)
'A/D conversion completed flag' (XE)
digit: Digital output value
t: Time (ms)
Setting method
1.
Set "Average processing setting" to "Time average", "Count average", or "Moving average".
[Navigation window]  [Parameter]  [Module Information]  Module model name  [Basic setting]  [A/D conversion
method]
2.
Set a value for "Time average/Count average/Moving average/Primary delay filter constant setting".
A/D conversion method
Time average
Count average
Moving average
digit
(3)
(4)
(2)
(5)
(1)
0
0
(a)
0
ON
OFF
Data transition in buffer memory
(a)
(1) + (2) + (3) + (4) + (5)
(2) + (3) + (4) + (5) + (6)
5
Sampling cycle
(6)
(8)
(9)
(12)
(7)
(10) (11)
1st storage (a)
2nd storage (b)
3rd storage (c)
(b)
(c)
(b)
(3) + (4) + (5) + (6) + (7)
5
Setting range
320 to 5000 (ms)
4 to 500 (times)
2 to 1000 (times)
t
(c)
5
1 FUNCTIONS
1.5 A/D Conversion Method
1
27