A/D Conversion Method - Mitsubishi Electric Melsec iQ-R Series User Manual

Hart-enabled analog-digital converter module
Hide thumbs Also See for Melsec iQ-R Series:
Table of Contents

Advertisement

1.5

A/D Conversion Method

An A/D conversion method can be set for each channel. The following shows available conversion methods.
• Sampling processing
• Averaging processing (time average, count average, moving average)
• Primary delay filter
Overview of A/D conversion
The A/D conversion is executed per channel.
■Sampling cycle
Sampling cycle is the internal A/D conversion cycle. The sampling cycle is fixed to 80ms regardless of the settings of the
number of conversion enabled channels.
■Conversion cycle
Digital output values are updated on the conversion cycle of sampling processing, averaging processing, or primary delay
filter. The following table lists the conversion cycles in each A/D conversion method.
A/D conversion method
Conversion cycle
Sampling processing
Sampling cycle
((The time set for Time average/Count average/Moving average/Primary delay filter constant setting)  Sampling cycle)
Time average
Sampling cycle
(The count set for Time average/Count average/Moving average/Primary delay filter constant setting)  Sampling cycle
Count average
Moving average
Sampling cycle
Primary delay filter
Sampling cycle
*1 Values after the decimal point are omitted.
*1
1 FUNCTIONS
1.5 A/D Conversion Method
1
25

Advertisement

Table of Contents
loading

Table of Contents