Setting Table - ABB REC 561 User Manual

Bay level control terminal
Table of Contents

Advertisement

ABB Network Partner AB
Version 1.0-00

6.3 Setting table

PARAMETER:
Operation
Program
Extendt1
t1S
t1
t2
t3
t4
tSync
tPulse
CutPulse
tReclaim
tInhibit
CB Ready
tTrip
Priority
tWait
Auto-reclosing - Single- and/or
three-phase
SETTING RANGE:
Off, Stand by, On
3ph, 2*3ph, 3*3ph, 4*3ph, 1ph, 1/3 ph,
1ph+3ph, 1ph/3ph+3ph
Off, On
(0.20 - 5.00)seconds
(0.20 - 60.00)seconds
(1 - 300)seconds
(1 - 300)seconds
(1 - 300)seconds
(0.5 - 5.0)seconds
(0.10 - 1.00)seconds
Off, On
(10 - 300)seconds
(5 - 30)seconds
CO, OCO
(0.2 - 1.0)seconds
None, Low, High
(30 - 300)seconds
1MRK 580 170-XEN
DESCRIPTION:
Auto-reclose operation
Auto-reclosing function
Extended dead time in case of carrier
channel failure
Open time for single phase auto-reclos-
ing
Open time for 3 phase auto-reclosing
Open time for second 3 phase auto-
reclosing
Open time for third 3 phase auto-reclos-
ing
Open time for fourth 3 phase auto-
reclosing
Auto-recloser maximum wait time for
synchrocheck
Circuit breaker closing pulse length
Shorten closing pulse at a new trip
Auto-reclose reclaim time
Inhibit reset time
Select type of circuit breaker ready sig-
nal
Block auto-reclosing for long trip dura-
tion
Priority selection for sequential reclosing
Maximum wait time from master
Page
5 - 81

Hide quick links:

Advertisement

Table of Contents
loading