ABB REC 561 User Manual page 548

Bay level control terminal
Table of Contents

Advertisement

ABB Network Partner AB
Version 1.0-00
PARAMETER:
SETTING RANGE: DESCRIPTION:
Operation
Off, On
RepInt
(0-3600)Seconds
EnAlarms
Off, On
EnAlRem
Off, On
Hysteres
(0-99999)A
LowAlarm
(0-99999)A
LowWarn
(0-99999)A
HiWarn
(0-99999)A
HiAlarm
(0-99999)A
EnDeadB
Off, On
DeadBand
(0-99999)A
EnIDeadB
Off, On
IDeadB
(0-99999)A
EnDeadBP
Off, On
Operation
Off, On
RepInt
(0-3600)Seconds
EnAlarms
Off, On
EnAlRem
Off, On
Hysteres
(0.0-9999.9)MW
LowAlarm
(0.0-9999.9)MW
LowWarn
(0.0-9999.9)MW
HiWarn
(0.0-9999.9)MW
Measurement of alternating
quantities
Mean current measuring channel
Operation of the measuring channel enabled (On) or disabled (Off)
Duration of time interval between two reports at periodic reporting
function. Setting to 0 disables the periodic reporting.
Produces an immediate event at operation of any alarm monitoring ele-
ment, when On
Produces an immediate event at reset of any alarm monitoring element,
when On.
Hysteresis for the set values of the monitoring elements in one measur-
ing channel.
Determines the operating value of the monitoring element which pro-
duces logical signal DA12-LOWALARM
Determines the operating value of the monitoring element which pro-
duces logical signal DA12-LOWARN
Determines the operating value of the monitoring element which pro-
duces logical signal DA12-HIWARN
Determines the operating value of the monitoring element which pro-
duces logical signal DA12-HIALARM
Enables (On) or disables (Off) the amplitude dead-band supervision
function
Width of the amplitude dead-band within the ADBS function
Enables (On) or disables (Off) the integrating dead-band supervision
function.
Determines the width of the band within the IDBS function. Be aware of
the sampling frequency
Enables (On) or disables (Off) the periodic dead-band reporting
Active power measuring channel
Operation of the measuring channel enabled (On) or disabled (Off)
Duration of time interval between two reports at periodic reporting
function. Setting to 0 disables the periodic reporting.
Produces an immediate event at operation of any alarm monitoring ele-
ment, when On
Produces an immediate event at reset of any alarm monitoring element,
when On.
Hysteresis for the set values of the monitoring elements in one measur-
ing channel.
Determines the operating value of the monitoring element which pro-
duces logical signal DA13-LOWALARM
Determines the operating value of the monitoring element which pro-
duces logical signal DA13-LOWARN
Determines the operating value of the monitoring element which pro-
duces logical signal DA13-HIWARN
1MRK 580 159-XEN
Page
7 - 29