1MRK 580 150-XEN
Page
6 - 94
7.2.10SWICONC
Apparatus control
Table 19: Input signals for SWICONC
IN:
SCxx-POSIND_V
SCxx-POS_O
SCxx-POS_C
SCxx-BLK_UPD
SCxx-PROC_UPD
SCxx-MA_UPD_O
SCxx-MA_UPD_C
SCxx-UPD_BLK
SCxx-SELECT
SCxx-FDB_SEL
SCxx-OPEN
SCxx-CLOSE
SCxx-EXECUTE
SCxx-CANCEL
SCxx-BLK_OPEN
SCxx-BLK_CLOS
SCxx-INT_LOCK
SCxx-AU_OP_V
Table 20: Output signals for SWICONC
OUT:
SCxx-OX
ABB Network Partner AB
DESCRIPTION:
Input for external position check function,
i.e. valid position of the apparatus
Input for open position indication
Input for close position indication
Blocking of updating of the position indica-
tion (pulse input from COMCON)
Resuming of updating of the position indica-
tion (pulse input from COMCON)
Input for manual setting of open position
(pulse input from COMCON)
Input for manual setting of close position
(pulse input from COMCON)
Input for blocking of updating (from BLK-
CONK at blocking of all apparatuses in a
bay)
Selection input (from BAYCON, signal
SELx)
Feedback selection input
Open direction for operation (pulse input
from COMCON)
Close direction for operation (pulse input
from COMCON)
Execution of operation (pulse input from
COMCON)
Cancelling of the selected operation (pulse
input from COMCON)
Blocking input for open direction
Blocking input for close direction
Operation blocked by conditions from the
interlocking module
Automatic operation permitted (signal from
BAYCON)
DESCRIPTION:
Indication that the apparatus is in open posi-
tion. Result of the input indication or block-
ing of the process updating or by the
manually entered open position
Version 1.0-00