1MRK 580 154-XEN
Page
7 - 14

8.2 Signal list

Table 2
IN:
DESCRIPTION:
MIn1-BLOCK
Blocks the reporting of new measured value by measuring channel No.1 on measuring
module n (n = 1...6)
MIn2-BLOCK
Blocks the reporting of new measured value by measuring channel No.2 on measuring
module n (n = 1...6)
MIn3-BLOCK
Blocks the reporting of new measured value by measuring channel No.3 on measuring
module n (n = 1...6)
MIn4-BLOCK
Blocks the reporting of new measured value by measuring channel No.4 on measuring
module n (n = 1...6)
MIn5-BLOCK
Blocks the reporting of new measured value by measuring channel No.5 on measuring
module n (n = 1...6)
MIn6-BLOCK
Blocks the reporting of new measured value by measuring channel No.6 on measuring
module n (n = 1...6)
MIn1-POSITION
Defines the position of the measuring module n (n = 1...6) within the terminal. It must be
configured to the corresponding output signal of the positioning block IOP.
OUT:
DESCRIPTION:
MIn1-ERROR
Represent the fault detected on complete measuring module n (n = 1...6). It signalises also
the wrong module on specified position. The signal is common for the complete measuring
module
MInm-LOWALARM Has the value equal to logical 1 when the measured input current on the measuring mod-
ule n (n = 1...6) for the measuring channel m (m = 1...6) decreases under the correspond-
ing set value LowAlarm.
MInm-LOWWARN
Has the value equal to logical 1 when the measured input current on the measuring mod-
ule n (n = 1...6) for the measuring channel m (m = 1...6) decreases under the correspond-
ing set value LowWarn.
MInm-HIWARN
Has the value equal to logical 1 when the measured input current on the measuring mod-
ule n (n = 1...6) for the measuring channel m (m = 1...6) increases over the corresponding
set value HiWarn.
MInm-HIALARM
Has the value equal to logical 1 when the measured input current on the measuring mod-
ule n (n = 1...6) for the measuring channel m (m = 1...6) increases over the corresponding
set value HiAlarm.
MInm-RMINAL
Has the value equal to logical 1 when the measured input current on the measuring mod-
ule n (n = 1...6) for the measuring channel m (m = 1...6) decreases under the correspond-
ing minimum set reach I_Min.
MInm-RMAXAL
Has the value equal to logical 1 when the measured input current on the measuring mod-
ule n (n = 1...6) for the measuring channel m (m = 1...6) increases over the corresponding
maximum set reach I_Max.
MInm-INPUTERR
Informs about the detected error within the measuring channel m (m = 1...6) on the meas-
uring module n (n = 1...6).
Direct current measuring unit
ABB Network Partner AB
Version 1.0-00