2.5 Pulse

2.6 Exclusive OR (XOR)

Configurable logic
If you need more timers than available in the terminals, you can use pulse
timers with AND or OR logics. Fig. 5 shows an application example of
how to realize a timer delayed on pick-up. Fig. 6 shows the realization of
a timer delayed on drop-out. Note that the resolution of the setting time
must be 0.2 s, if the connected logic has a cycle time of 200 ms.
Pulse
INPUT
0-50.0 s
T
Fig. 5
Realization example of a timer delayed on pick-up
INV
INPUT OUT
0-50.0 s
Fig. 6
Realization example of a timer delayed on drop-out
The configuration logic pulse timer TP (Fig. 7) has a settable length of a
pulse between 0.01 s and 50.00 s in steps of 0.01 s. The input signal for
each pulse timer has the designation TPnn-INPUT, where nn runs from 01
to 10 for REL 531 and to 50 for REC 561 and presents the serial number
of the logic block. Each pulse timer has one output, designated by TPnn-
OUT. The pulse timer is not retriggable, that is, it can be restarted first
after that the time T has elapsed.
TPnn
Fig. 7
Block diagram of the Pulse function
The configuration logic exclusive OR (XOR) (Fig. 8) has two inputs, des-
ignated XOnn-INPUTm, where nn runs from 01 to 39 for REC 561 and
presents the serial number of the block, and m presents the serial number
ABB Network Partner AB
FIXED-ON
OUT
FIXED-OFF
Pulse
INPUT
OUT
T
OUT
INPUT
T
Time delay 0.01-50.00 s
Version 1.0-00
AND
OUT
INPUT1
INPUT2
NOUT
INPUT3
INPUT4N
(X80161-5)
OR
INPUT1
OUT
NOUT
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
(X80161-6)
(X80161-7)