3.3 Remote
Communication, SMS
or SCS
Installation and commissioning
the built-in MMI. The other end of the cable is plugged directly into the
COM-port of the PC. The cable includes an optical contact, an opto/elec-
trical converter and an electrical cable with a standard 9-pole D-sub con-
tact. This gives you a disturbance-free and safe communication with the
terminal.
When communicating with a PC, the setting of the slave number and baud
rate (communication speed) must be equal in the program and in the ter-
minal. For further instructions on how to set these parameters in the PC
program, see the User's Guide of SMS-BASE and of the SM/REx 5xx.
The setting of the slave number and baud rate of the front port of the ter-
minal is done on the built-in MMI at:
Configuration
SPA Comm
Front
Setting can be performed via either of the optical ports at the rear of the
terminal. When a PC is connected to the SMS system, SMS-BASE and
the appropriate SM/REx 5xx modules are used. For configuration,
CAP 531 can be used with SMS. For the collection of analogue data to a
PC, RECOM is also required in the PC. Setting can also be done via the
SCS system based on MicroLIBRARY.
For all setting and configuration via the optical ports on the rear, set the
Setting Restrictions to Open. Otherwise, no setting is allowed via the rear
communication ports. This setting applies for both the SPA port and the
LON port. This parameter can only be set on the local MMI, and is
located at:
Configuration
SPAComm
Rear
SettingRestrict
You can also permit changes between active setting groups with
ActGrpRestrict in the same menu section.
When communicating with SMS or SCS via the SPA port, the setting of
the slave number and baud rate (communication speed) must be equal in
the computer program and in the terminal. For further instructions on how
to set these parameters in the SMS, see the User's Guide of SMS-BASE
and of the SM/REx 5xx.
The setting of the slave number and baud rate of the rear SPA port of the
terminal is done on the built-in MMI at:
Configuration
SPA Comm
Rear