ABB REC 561 User Manual page 477

Bay level control terminal
Table of Contents

Advertisement

1MRK 580 151-XEN
Page
6 - 192
Interlocking
Table 3: Input signals for ABC_BC
IN:
IGxx-EXVVA_BC
IGxx-Q0_O_EX1
IGxx-Q0_O_EX2
IGxx-Q0_O_EX3
IGxx-Q1EX1
IGxx-Q1EX2
IGxx-Q1EX3
IGxx-Q20EX1
IGxx-Q20EX2
IGxx-Q20EX3
IGxx-Q2EX1
IGxx-Q2EX2
IGxx-Q7EX1
IGxx-Q7EX2
Table 4: Output signals for ABC_BC
OUT:
IGxx-Q0OPREL
IGxx-Q0OPITL
IGxx-Q0CLREL
IGxx-Q0CLITL
IGxx-Q1REL
IGxx-Q1ITL
IGxx-Q20REL
IGxx-Q20ITL
IGxx-Q7REL
IGxx-Q7ITL
ABB Network Partner AB
DESCRIPTION:
Signal is 1 if the interlocking programs in all
bays connected to the BC busbars are run-
ning
Input for an external open condition for
apparatus Q0
Input for an external open condition for
apparatus Q0
Input for an external open condition for
apparatus Q0
Input for an external condition for apparatus
Q1
Input for an external condition for apparatus
Q1
Input for an external condition for apparatus
Q1
Input for an external condition for apparatus
Q20
Input for an external condition for apparatus
Q20
Input for an external condition for apparatus
Q20
Input for an external condition for apparatus
Q2
Input for an external condition for apparatus
Q2
Input for an external condition for apparatus
Q7
Input for an external condition for apparatus
Q7
DESCRIPTION:
Opening of Q0 is allowed
Opening of Q0 is forbidden
Closing of Q0 is allowed
Closing of Q0 is forbidden
Switching of Q1 is allowed
Switching of Q1 is forbidden
Switching of Q20 is allowed
Switching of Q20 is forbidden
Switching of Q7 is allowed
Switching of Q7 is forbidden
Version 1.0-00

Hide quick links: