4 Appendix

4.1 Terminal diagrams

4.2 Signal list

IN:
DESCRIPTION:
TRIP-BLOCK
Inhibits the operation of tripping logic.
TRIP-EXTTRIP
Initiates the instantaneous three-phase tripping. Disabled when the function is out of oper-
ation.
TRIP-EXTL1
External tripping related to phase L1.
TRIP-EXTL2
External tripping related to phase L2.
TRIP-EXTL3
External tripping related to phase L3.
TRIP-TRSPE
Information on necessary tripping in one phase. It causes instantaneous single-phase trip-
ping if some of the phase selection signals are present. If not, three-phase tripping,
delayed for 50 ms, is initiated.
TRIP-PSL1
Necessary condition for single phase trip in phase L1. Usually connected to protection
functions with phase-selective operation.
TRIP-PSL2
Necessary condition for single phase trip in phase L2. Usually connected to protective
functions with phase-selective operation.
Tripping logic
THREE-PHASE TRIPPING LOGIC
TRIP_BLOCK
TRIP_TESTBLCK
TRIP_EXTTRIP
TRIP_EXTL1
TRIP_EXTL2
TRIP_EXTL3
TRIP_TRSP
TRIP_TRTP
SINGLE AND/OR THREE-PHASE TRIPPING LOGIC
TRIP_BLOCK
TRIP_TESTBLCK
TRIP_TRTP
TRIP_EXTTRIP
TRIP_EXTL1
TRIP_EXTL2
TRIP_EXTL3
TRIP_TRSPE
TRIP_PSL1
TRIP_PSL2
TRIP_PSL3
TRIP_TRSPZ
TRIP_PTPTRIP
Fig. 4
Simplified terminal diagram for the function
TRIP_TRIPL1
TRIP_TRIPL2
TRIP_TRIPL3
TRIP_GTRIP
TRIP_TPTRIP
TRIP_SPTRIP
TRIP_TRIPL1
TRIP_TRIPL2
TRIP_TRIPL3
TRIP_GTRIP
TRIP_TPTRIP
TRIP_SPTRIP
1MRK 580 120-XEN
Page
5 - 7
(X80120-4)