ABB REC 561 User Manual page 371

Bay level control terminal
Table of Contents

Advertisement

1MRK 580 150-XEN
Page
6 - 86
Apparatus control
Table 13: Input signals for COMCON
IN:
COxx-L_SEL_C
COxx-L_OPEN
COxx-L_CLOSE
COxx-L_IR_OVR
COxx-LOCAL
COxx-AU_SEL_O
COxx-AU_SEL_C
COxx-AU_OPEN
COxx-AU_CLOSE
COxx-AU_CANC
COxx-SEL_SEQ
Table 14: Output signals for COMCON
OUT:
COxx-RQ_SEL
COxx-OPEN
COxx-CLOSE
COxx-EXECUTE
COxx-CANCEL
COxx-OVERRIDE
COxx-LO_OP_T
COxx-RES_ERR
COxx-R_OP
COxx-S_OP
COxx-BLK_OP
ABB Network Partner AB
DESCRIPTION:
Selection for closing the apparatus from
Local
Execute command for opening the appara-
tus from Local
Execute command for closing the apparatus
from Local
Input for overriding selection and reserva-
tion from Local
Input for indicating Local as valid operator
place
Selection for opening the apparatus from an
automatic function (pulse input)
Selection for closing the apparatus from an
automatic function (pulse input)
Execute command for opening the appara-
tus from an automatic function (pulse input)
Execute command for closing the apparatus
from an automatic function (pulse input)
Input for cancelling an operation from an
automatic function (pulse input)
A sequence program is performing an oper-
ation
DESCRIPTION:
Request selection output
Open direction output
Close direction output
Output signal to execute the operation
Output signal to cancel any operation
before an execute command
Output signal to override an interlocking and
reservation
Indication of a long operation time
Indication of a failure in the reservation
MMI indication stating that Remote is valid
operator place
MMI indication stating that Station is valid
operator place
Output signal for blocking the operation
(pulse output)
Version 1.0-00

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents