ABB REC 561 User Manual page 550

Bay level control terminal
Table of Contents

Advertisement

ABB Network Partner AB
Version 1.0-00
PARAMETER:
SETTING RANGE: DESCRIPTION:
Operation
Off, On
RepInt
(0-3600)Seconds
EnAlarms
Off, On
EnAlRem
Off, On
Hysteres
(0.0-99.9)Hz
LowAlarm
(0.0-99.9)Hz
LowWarn
(0.0-99.9)Hz
HiWarn
(0.0-99.9)Hz
HiAlarm
(0.0-99.9)Hz
EnDeadB
Off, On
DeadBand
(0.0-99.9)Hz
EnIDeadB
Off, On
IDeadB
(0.0-99.9)Hz
EnDeadBP
Off, On
EventMask f
No Events, Report
Events
EventMask Q
No Events, Report
Events
EventMask P
No Events, Report
Events
EventMask I
No Events, Report
Events
EventMask U
No Events, Report
Events
EventMask I5
No Events, Report
Events
EventMask I4
No Events, Report
Events
Measurement of alternating
quantities
Frequency measuring channel
Operation of the measuring channel enabled (On) or disabled (Off)
Duration of time interval between two reports at periodic reporting
function. Setting to 0 disables the periodic reporting.
Produces an immediate event at operation of any alarm monitoring ele-
ment, when On
Produces an immediate event at reset of any alarm monitoring element,
when On.
Hysteresis for the set values of the monitoring elements in one measur-
ing channel.
Determines the operating value of the monitoring element which pro-
duces logical signal DA15-LOWALARM
Determines the operating value of the monitoring element which pro-
duces logical signal DA15-LOWARN
Determines the operating value of the monitoring element which pro-
duces logical signal DA15-HIWARN
Determines the operating value of the monitoring element which pro-
duces logical signal DA15-HIALARM
Enables (On) or disables (Off) the amplitude dead-band supervision
function
Width of the amplitude dead-band within the ADBS function
Enables (On) or disables (Off) the integrating dead-band supervision
function.
Determines the width of the band within the IDBS function. Be aware of
the sampling frequency
Enables (On) or disables (Off) the periodic dead-band reporting
Reporting of events to the station control system (SCS) via LON
port
Enables (Report Events) or disables (No Events) reporting of events
from channel DA15 to the SCS
Enables (Report Events) or disables (No Events) reporting of events
from channel DA14 to the SCS
Enables (Report Events) or disables (No Events) reporting of events
from channel DA13 to the SCS
Enables (Report Events) or disables (No Events) reporting of events
from channel DA12 to the SCS
Enables (Report Events) or disables (No Events) reporting of events
from channel DA11 to the SCS
Enables (Report Events) or disables (No Events) reporting of events
from channel DA10 to the SCS
Enables (Report Events) or disables (No Events) reporting of events
from channel DA09 to the SCS