ABB REC 561 User Manual page 601

Bay level control terminal
Table of Contents

Advertisement

1MRK 580 188-XEN
Page
9 - 2
2 Application
2.1 General
Default configuration REC 561
The default configuration consists of type solutions for a double busbar
and single, circuit-breaker arrangement that includes three disconnectors
and one earthing switch. Use the copy/past and find/replace commands in
CAP 531 to extend the number of apparatuses and bays (option). Connec-
tions of optional functions are not in the default configuration, but can be
found under the functions respectively in the User's Guide for REC 561
or when the function is connected to the apparatus control function in
Apparatus Control (1MRK 580 150-XEN).
The configuration is divided into several worksheets, which are com-
mented below.
For this default configuration, the function selector in the CAP 531 has
these settings:
Table 1: Selected functions in the default configuration
Function group
Selector
AppControlType
APCACTIVE
AppControlType
APCGT8BAYS
AppControlType
APCSELSUP
AppControlType
APCSYNC
I/O-module01
Type_IO1
I/O-module02
Type_IO2
I/O-module03
Type_IO3
I/O-module04
Type_IO4
I/O-module05
Type_IO5
I/O-module06
Type_IO6
I/O-module07
Type_IO7
I/O-module08
Type_IO8
I/O-module09
Type_IO9
I/O-module10
Type_IO10
I/O-module11
Type_IO11
I/O-module12
Type_IO12
I/O-module13
Type_IO13
InterlockType
ILTYPE1
The settings in table 1 mean:
• The apparatus control function is activated.
• No bays in the terminal have more than 8 apparatuses.
• No external selection relays are used.
• External synchro-check is used.
• The binary input module of type BIM is defined as I/O module 1.
ABB Network Partner AB
Value
1=ON
0=0 bay > 8 app
0=None
1=External/None Synchrocheck
1=BIM
2=BOM
0=None
0=None
0=None
0=None
0=None
0=None
0=None
0=None
0=None
0=None
0=None
2=ABC_LINE
Version 1.0-00