ABB REC 561 User Manual page 28

Bay level control terminal
Table of Contents

Advertisement

ABB Network Partner AB
Version 1.0-00
Table 2: Influencing factors, permissible influence
Dependence on
Ambient temperature
Ripple in auxiliary dc voltage
Interruption in auxiliary dc voltage
without resetting
correct function
restart time
Table 3: Electromagnetic compatibility tests
Test
1 MHz burst disturbance
Electrostatic discharge
Fast transient disturbance
Radiated electromagnetic field dis-
turbance
Table 4: Insulation tests (reference standard: IEC 255-5)
Test
Dielectric test
Impulse voltage test
Insulation resistance
Table 5: Mechanical tests
Test
Vibration
Shock and bump
Seismic
Requirements and basic technical
data - REC 561
Within nominal range
0,01 % / °C
Negligible
< 50 ms
0 - ∞
< 100 s
Type test values
2,5 kV
8 kV
4 kV
10 V/m, (25-1000) MHz
Type test values
2,0 kV ac, 1 min
5 kV, 1,2/50 µs, 0,5 J
>100 MΩ at 500 V dc
Type test values
Class I
Class I
Class I
Page
Within operative range
Correct function
Correct function
< 50 ms
0 - ∞
< 100 s
Reference standards
IEC 255-22-1, Class III
IEC 255-22-2, Class III
IEC 255-22-4, Class IV
IEC 255-22-3, Class III
Draft IEEE/ANSI C37.90.2
Reference standards
IEC 255-21-1
IEC 255-21-2
IEC 255-21-3
2 - 23