Technical Data - ABB REC 561 User Manual

Bay level control terminal
Table of Contents

Advertisement

Page
2 - 22

6 Technical data

Table 1: Energizing quantities, rated values and limits
Quantity
Current
Operative range
Burden
Ac voltage Ph-Ph
Operative range
Burden
Frequency
Auxiliary dc voltage EL
power consumption
Binary input(8)/output(12) module
dc voltage RL
power consumption
Binary input module
dc voltage RL
power consumption
Binary output module
power consumption
mA input module
input range
input resistance
power consumption
Ambient temperature
Ripple in dc auxiliary voltage
Relative humidity
*) max. 350 A for 1 s when COMBIFLEX test switch included together with the product
Requirements and basic technical
data - REC 561
basic terminal
each I/O-board
each output relay
RL24 = (24/30)V
RL48 = (48/60)V
RL110 = (110/125)V
RL220 = (220/250)V
each input-board
RL24 = (24/30)V
RL48 = (48/60)V
RL110 = (110/125)V
RL220 = (220/250)V
each output-board
each output relay
each mA-board
each mA input
Rated value
I
= 1 or 5 A
r
(0,2-4) × I
cont.
r
(0,2-100) × I
*)
for 1 s
r
< 0,25 VA at I
r
U
= 100/110/115/120 V
r
1,5 × U
cont.
r
2,5 × U
for 1 s
r
< 0,2 VA at U
r
f
= 50/60 Hz
r
U
= (48-250) V
r
≤ 16 W
RL24 = (24/30)V
RL48 = (48/60)V
RL110 = (110/125)V
RL220 = (220/250)V
≤ 1 W
≤ 0,15 W
max. 0,05 W/input
max. 0,1 W/input
max. 0,2 W/input
max. 0,4 W/input
RL24 = (24/30)V
RL48 = (48/60)V
RL110 = (110/125)V
RL220 = (220/250)V
≤ 0,5 W
max. 0,05 W/input
max. 0,1 W/input
max. 0,2 W/input
max. 0,4 W/input
≤ 1,0 W
≤ 0,25 W
± 5, ± 10, ± 20 mA
0-5, 0-10, 0-20, 4-20 mA
R
= 194 Ohm
in
≤ 4 W
≤ 0,1 W
20° C
max. 2 %
(10-90) %
ABB Network Partner AB
Version 1.0-00
Nominal range
(0,2-30) x I
r
(80-120) % of U
r
± 5 %
± 20 %
± 20 %
± 20 %
± 20 %
± 20 %
± 20 %
± 20 %
± 20 %
± 20 %
± 10 %
-5° C to +55° C
max. 12 %
(10-90) %