(M) Monitor display and monitor output signal
5.11.2

Monitor indicator selection using operation panel or via communication

The monitored item to be displayed on the operation panel or the parameter unit can be selected.
Pr.
52
M100
774
M101
775
M102
776
M103
992
M104
170
M020
563
M021
268
M022
891
M023
171
M030
564
M031
290
M044
1018
M045
1106
M050
1107
M051
5 - 344
Name
Operation panel main monitor
selection
Operation panel monitor
selection 1
Operation panel monitor
selection 2
Operation panel monitor
selection 3
Operation panel setting dial
push monitor selection
Watt-hour meter clear
Energization time carrying-
over times
Monitor decimal digits
selection
Cumulative power monitor
digit shifted times
Operation hour meter clear
Operating time carrying-over
times
Monitor negative output
selection
Monitor with sign selection
Torque monitor filter
Running speed monitor filter
Initial value
Setting range
0, 5 to 14, 17 to 20,
0
22 to 36, 38, 40 to
(output
46, 50 to 57, 61, 62,
frequency)
64, 67, 71 to 74, 87
to 98, 100
1 to 3, 5 to 14,
17 to 20, 22 to 36,
38, 40 to 46, 50 to
9999
57, 61, 62, 64, 67, 71
to 74, 87 to 98, 100,
9999
0 to 3, 5 to 14,
0
17 to 20, 22 to 36,
38, 40 to 46, 50 to
(Set
57, 61, 62, 64, 67, 71
frequency)
to 74, 87 to 98, 100
0
10
9999
9999
(0 to 65535)
0
(Read-only)
0
9999
1
9999
0 to 4
9999
9999
0
9999
9999
(0 to 65535)
0
(Read-only)
0
0 to 7
0
9999
9999
0 to 5 s
9999
9999
0 to 5 s
9999
9999
Parameters
Description
Select the monitor to be displayed
on the operation panel and
parameter unit.
Refer to page 5-345 for the monitor
description.
The output frequency, output
current and output voltage monitor
that are displayed in monitor mode
on the operation panel and
parameter unit can be switched to a
specified monitor.
9999: Follows the Pr. 52 setting.
Select the monitor to be displayed
when the setting dial on the
operation panel is pushed.
Set "0" to clear the watt-hour meter
monitor.
Set the maximum value for
monitoring via communication. Set it
in the range of 0 and 9999 kWh.
Set the maximum value for
monitoring via communication. Set it
in the range of 0 and 65535 kWh.
Displays the numbers of times that
the cumulative energization time
monitor exceeded 65535 h. Read-
only.
Displays as integral value.
Displays in 0.1 increments.
No function
Set the number of times to shift the
cumulative power monitor digit.
The monitor value is clamped at the
maximum value.
No shift
Monitor value is cleared when it
exceeds the maximum value.
Set "0" to clear the operation hour
monitor.
The read value is always 9999.
Nothing happens when "9999" is set.
Displays the numbers of times that
the operating time monitor
exceeded 65535 h. Read-only.
Set the availability of output with a
minus sign for the terminal AM, the
operation panel display, or
monitoring via communication.
(Refer to page 5-355.)
Select items to be displayed with
minus signs.
The filter time constant is selectable
for monitoring of the torque. A larger
setting results in slower response.
0.3 s filter
The filter time constant is selectable
for monitoring of the running speed.
A larger setting results in slower
response.
0.08 s filter