Main circuit terminals
400 V class (440 V input power supply (with 150% rated current for one minute))
Terminal
Applicable
screw
inverter model
FR-A840-
size
00023(0.4K) to
M4
00126(3.7K)
00170(5.5K)
M4
00250(7.5K)
M4
00310(11K)
M5
00380(15K)
M5
00470(18.5K)
M6
00620(22K)
M6
00770(30K)
M6
00930(37K)
M8
01160(45K)
M8
01800(55K)
M8
02160(75K)
M10
02600(90K)
M10
03250(110K)
M10(M12)
03610(132K)
M10(M12)
04320(160K)
M12(M10)
04810(185K)
M12(M10)
05470(220K)
M12(M10)
06100(250K)
M12(M10)
06830(280K)
M12(M10)
Tab. 2-10:
Cable size (400 V class)
For the FR-A820-03160(55K) or lower and FR-A840-01800(55K) or lower, it is the gauge of a cable
with the continuous maximum permissible temperature of 75 °C (HIV cable (600 V grade heat-
resistant PVC insulated wire), etc.). It assumes a surrounding air temperature of 50 °C or lower and
the wiring distance of 20 m or shorter.
For the FR-A820-03800(75K) or higher, FR-A840-02160(75K) or higher, it is the gauge of the cable
with the continuous maximum permissible temperature of 90 °C or higher. (LMFC (heat resistant
flexible cross-linked polyethylene insulated cable), etc.). It assumes a surrounding air temperature
of 50 °C or lower and in-enclosure wiring.
For all the 200 V class capacities and FR-A840-01160(45K) or lower, it is the gauge of a cable with
the continuous maximum permissible temperature of 75 °C (THHW cable). It assumes a surround-
ing air temperature of 40°C or lower and the wiring distance of 20 m or shorter.
For the FR-A840-01800(55K) or higher, it is the gauge of a cable with the continuous maximum
permissible temperature of 90°C (THHN cable). It assumes a surrounding air temperature of 40 °C
or lower and in-enclosure wiring. (Selection example for use mainly in the United States.)
For the FR-A820-00770(15K) or lower and the FR-A840-01160(45K) or lower, it is the gauge of a
cable with the continuous maximum permissible temperature of 70 °C (PVC cable). It assumes a
surrounding air temperature of 40 °C or lower and the wiring distance of 20 m or shorter.
For the FR-A820-00930(18.5K) or higher and the FR-A840-01800(55K) or higher, it is the gauge of
a cable with the continuous maximum permissible temperature of 90 °C (XLPE cable). It assumes
a surrounding air temperature of 40 °C or lower and in-enclosure wiring. (Selection example for
use mainly in Europe.)
2 - 38
Crimping
terminal
Tighten-
ing
torque
R/L1,
R/L1,
Nm
S/L2,
U, V, W
S/L2,
T/L3
1.5
2-4
2-4
1.5
2-4
2-4
1.5
5.5-4
5.5-4
2.5
5.5-5
5.5-5
2.5
8-5
5.5-5
4.4
14-6
8-6
4.4
14-6
14-6
4.4
22-6
22-6
7.8
22-8
22-8
7.8
38-8
38-8
7.8
60-8
60-8
14.7
60-10
60-10
14.7
60-10
60-10
14.7
80-10
80-10
14.7
100-10 100-10
24.5
150-12 150-12
24.5
150-12 150-12
46
100-12 100-12 2×100
46
100-12 100-12 2×100
46
150-12 150-12 2×125
HIV cables, etc. (mm²)
Earthing
(ground-
U, V, W P/+, P1
ing)
T/L3
cable
2
2
2
2
2
2
3.5
3.5
3.5
3.5
3.5
3.5
5.5
5.5
5.5
5.5
8
5.5
8
5.5
14
8
14
8
14
14
22
14
22
22
22
14
22
22
22
14
38
38
38
22
60
60
60
22
60
60
60
22
60
60
80
22
80
80
80
38
100
100
100
38
125
125
150
38
150
150
150
38
2×100
2×100
60
2×100
2×125
60
2×125
2×125
60
Installation and wiring
Cable gauge
AWG/MCM
PVC cables, etc. (mm²)
R/L1,
R/L1,
S/L2,
U, V, W
S/L2,
U, V, W
T/L3
T/L3
14
14
2.5
12
14
2.5
12
12
4
10
10
6
8
10
10
6
8
16
6
6
16
4
4
25
4
4
25
1
2
50
1/0
1/0
50
1/0
1/0
50
3/0
3/0
50
3/0
3/0
70
4/0
4/0
95
250
250
120
300
300
150
2×4/0
2×4/0
2×95
2×4/0
2×4/0
2×95
2×250
2×250
2×120
Earthing
(ground-
ing)
cable
2.5
2.5
2.5
4
4
4
6
10
6
10
10
16
16
16
25
16
25
16
50
25
50
25
50
25
50
25
70
35
95
50
120
70
150
95
2×95
95
2×95
95
2×120
120

Hide quick links: