Ethernet communication (FR-A800-E)
5.22.3

CC-Link IE Field Network Basic (FR-A800-E)

The CC-Link IE Field Network Basic enables CC-Link IE communication using the general-purpose
Ethernet-based technology. The CC-Link IE Field Network Basic is suited to small-scale equipment for
which high-speed control is not necessary, and can coexist with the standard Ethernet TCP/IP (HTTP,
FTP, etc.).
Pr.
541
N100
544
N103
804
D400
810
H700
The setting is applied after an inverter reset or power-ON.
Communication specifications
Item
Transmission speed
Communication method
Connectable units
Topology
Number of occupied stations
Maximum number of links per station
Reference response time
Tab. 5-385: CC-Link IE Field Network Basic communication specifications
The reference response time is the period from when the inverter receives a command from the
master until the inverter returns the response to the master.
Initial setting
● To select the CC-Link IE Field Network Basic for the application, set "61450"" in any of Pr. 1427 to
Pr. 1429 (Ethernet function selection 1 to 3). (Refer to page 5-677.)
● To limit the network devices that send the command through the Ethernet network (CC-Link IE
Field Network Basic), set the range of IP addresses (Pr. 1449 to Pr. 1454). (Refer to page 5-681.)
● Set the interval of the communication check (signal loss detection) time in Pr. 1432 "Ethernet
communication check time interval" for all devices with IP addresses in the range specified for
Ethernet command source selection (Pr. 1449 to Pr. 1454). (Refer to page 5-682.)
5 - 802
Name
Frequency command sign
selection
CC-Link extended setting
Torque command source
selection
Torque limit input method
selection
Initial
Setting
Description
value
range
0
Frequency command without sign
0
1
Frequency command with sign
0, 1, 12, 14,
18, 24, 28,
The function of the remote registers can be extended
0
100, 112,
when the CC-Link IE Field Network Basic is used.
114, 118, 128
In the torque control mode, the torque command
0
0 to 6
source can be selected.
0
0 to 2
The torque limit input method can be selected.
Description
100 Mbps
UDP/IP
Master: 1
Slave: up to 64
Star
1
RX
64 (8 bytes)
RY
64 (8 bytes)
RWr
32 (64 bytes)
RWw
32 (64 bytes)
Within 15 ms
Parameters