Ethernet IP address for command source selection (Pr. 1449 to Pr. 1454)
● To limit the network devices that send the operation or speed command through the Ethernet
network (Modbus®/TCP or CC-Link IE Field Network Basic), set the range of IP addresses of the
devices.
● When Pr. 1449 to Pr. 1452 = "0 (initial value)", no IP address is specified for sending commands
through the Ethernet network. In this case, operation through the Ethernet network (Modbus®/
TCP or CC-Link IE Field Network Basic) is not available.
● When four or more clients attempt a connection to the inverter during Modbus®/TCP communi-
cation, the connection attempted from outside of the IP address range set for Ethernet command
source selection may be forced to be closed.
● The setting range for command source selection depends on the settings in Pr. 1451 and Pr. 1453,
and Pr. 1452 and Pr. 1454. (Either of the settings can be larger than the other in Pr. 1451 and
Pr. 1453, and Pr. 1452 and Pr. 1454.)
Example
Setting example 1:
In this case, the IP address range for command source selection via Ethernet communication is
"192.168.x (1 to 3).xxx (100 to 150)".
command source selection
Command source selection
Fig. 5-333:
Example
Setting example 2:
In this case, the IP address range for command source selection via Ethernet communication is
"192.168.2.xxx (50 to 100)".
Command source selection
Fig. 5-334:
● When "9999 (initial value)" is set in Pr. 1453 and Pr. 1454, the range is invalid.
FR-A800
Pr. 1449
Ethernet IP address for
192
range setting for the
Ethernet IP address
Ethernet IP address for command source selection setting example 1
Ethernet IP address for
command source selection
range setting for the
Ethernet IP address
Ethernet IP address for command source selection setting example 2
(N) Operation via communication and its settings
Pr. 1450
Pr. 1451
168
The range is between
the values set in both
parameters.
Pr. 1453
Pr. 1449
Pr. 1450
Pr. 1451
192
168
The range is between
the values set in both
parameters.
Pr. 1453
Pr. 1452
1
100
The range is between the
values set in both
parameters.
Pr. 1454
3
150
Pr. 1452
2
100
Pr. 1454
9999
50
I003112A