Inverter Output Shutoff Signal - Mitsubishi Electric FR-A820-00046 Instruction Manual

Fr-a800 series
Hide thumbs Also See for FR-A820-00046:
Table of Contents

Advertisement

Parameters
5.12.9

Inverter output shutoff signal

The inverter output can be shut off with the MRS signal. The logic of the MRS signal can also be se-
lected.
Pr.
17
T720
About output shutoff signal (MRS signal)
● When the Output stop (MRS) signal is turned ON while operating the inverter, inverter output is
instantaneously shut off.
● The response time of the MRS signal is within 2 ms.
MRS signal
STF (STR)
signal
● Terminal MRS may be used as described below.
– To use a mechanical brake (e.g. electromagnetic brake) to stop the motor
The inverter output is shut off when the mechanical brake operates.
– To provide interlock to disable operation by the inverter
With the MRS signal ON, the inverter cannot be operated even if the start signal is entered into
the inverter.
– To coast the motor to a stop
When the start signal is turned OFF, the inverter decelerates the motor to a stop in the preset
deceleration time, but when the MRS signal is turned ON, the motor coasts to a stop.
MRS signal logic inversion (Pr. 17 = "2")
When Pr.17 = "2", the MRS signal can be changed to normally closed (NC contact) specification. The in-
verter will shut off the output with MRS signal turned ON (opened).
Setting value "0" *
Output
stop
* Initial value
FR-A800
Name
MRS input selection
Motor coasts
to stop
Time
ON
ON
Setting value "2"
Output
stop
MRS
PC
PC
(T) Multi-Function Input Terminal Parameters
Initial
Setting
Description
value
range
0
Normally open input
Normally closed input
2
(NC contact input specification)
0
External terminal: Normally closed input
(NC contact input specification)
4
Communication: Normally open input
Fig. 5-213:
Output shutoff signal
Fig. 5-214:
Connection of the MRS terminal in source logic
MRS
I002653E
I002772E_G
5 - 443