Cc-Link Ie Field Network Function Setting (Fr-A800-Gf) - Mitsubishi Electric FR-A820-00046 Instruction Manual

Fr-a800 series
Hide thumbs Also See for FR-A820-00046:
Table of Contents

Advertisement

Parameters
5.15.7

CC-Link IE Field Network function setting (FR-A800-GF)

Use the following parameters to perform required settings for CC-Link IE Field Network communica-
tion between the inverter and other stations.
● For the details of the CC-Link IE Field Network, refer to page 5-747.
● For the inverter operation at communication error, refer to page 5-626.
● Set the parameters other than Pr. 434, Pr. 435, and Pr. 541 in the same way as when a communi-
cation option is used.
Pr.
434
N110
435
N111
541
N100
Network number and station number setting (Pr. 434, Pr. 435)
● Set the inverter network number in Pr. 434 "Network number (CC-Link IE)".
● The setting range of Pr. 434 is "0 to 255", but its active range is "1 to 239". The values out of the
active range are invalid because such values cannot be transmitted to the master station.
● Use Pr. 435 "Station number (CC-Link IE)" to set station number of the inverter.
● The setting range of Pr. 435 is "0 to 255", but its active range is "1 to 120". The values out of the
active range are invalid because such values cannot be transmitted to the master station.
NOTES
Use different station numbers for different devices. (If different devices have the same station
number, the communication cannot be performed properly. If an error occurs due to a duplicated
number, re-assign the station numbers, then reset the master station or the inverter power. )
Station numbers do not have to be consecutive numbers.
The Pr. 434 and Pr. 435 settings are applied after an inverter reset or next power-ON.
FR-A800
Name
Network number
(CC-Link IE)
Station number
(CC-Link IE)
Frequency command sign
selection
(N) Operation via communication and its settings
Initial
Setting
Description
value
range
0
0 to 255
Set the inverter network number.
0
0 to 255
Set the inverter station number.
0
Frequency command without sign
0
1
Frequency command with sign
5 - 673