Parameters
Modbus® register
The following shows the Modbus® registers for system environment variables (read/write), real time
monitor items (read), parameters (read/write), faults history data (read/write), and model information
monitor items (read).
● System environment variables
Register
40002
40003
40004
40006
40007
40009
40010
40014
40015
Tab. 5-379: System environment variable
Communication parameter settings are not cleared.
At a write, the data is set as the control input command.
At a read, the data is read as the inverter running status.
At a write, the data is set as the operation mode setting.
At a read, the data is read as the operation mode setting.
Bit
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Tab. 5-380: Inverter status/control input command
The signal within parentheses ( ) is the initial status. The input signal function can be changed using
Pr. 180 to Pr. 189 (input terminal function selection) (page 5-439).
JOG operation/automatic restart after instantaneous power failure/start self-holding selection/
reset cannot be controlled over a network, so in the initial status bit 6, bit 9, bit 11, and bit 12 are
invalid. To use bit 6, bit 9, bit 11, and bit 12, change the signal by Pr. 185, Pr.186, Pr. 188, or Pr. 189.
The inverter run enable signal is in the initial status for the separated converter type.
FR-A800
Definition
Inverter reset
Parameter clear
All parameter clear
Parameter clear
All parameter clear
Inverter status/control input command
Operation mode/inverter setting
Running frequency (RAM value)
Running frequency (EEPROM value)
Control input command
Stop command
Forward rotation command
Reverse rotation command
RH (High-speed operation command)
RM (Middle-speed operation command)
RL (Low-speed operation command)
JOG (Jog operation selection)
RT (Second function selection)
AU (Terminal 4 input selection)
CS (Selection of automatic restart after instantaneous
power failure)
MRS (Output stop)
STP (STOP) (Start self-holding selection)
RES (Inverter reset)
0
0
0
Ethernet communication (FR-A800-E)
Read/Write
Remarks
Write
Any value can be written
Write
Set H965A for the write value.
Write
Set H99AA for the write value.
Write
Set H5A96 for the write value.
Write
Set HAA99 for the write value.
Read/Write
Refer to the following table (tab. 5-380).
Read/Write
Refer to the following table (tab. 5-380).
The display can be changed to the rotations
Read/Write
per minute using Pr. 37, Pr. 144 and Pr. 811.
Write
(Refer to page 5-341.)
Definition
Inverter status
RUN (Inverter running)
During forward rotation
During reverse rotation
SU (Up to frequency)
OL (Overload warning)
IPF (Instantaneous power failure)
FU (Output frequency detection)
ABC1 (Fault)
ABC2 (⎯)
Safety monitor output
0
0
0
0
0
Fault occurrence
5 - 797