Commissioning
No.
65
This communication object is enabled if the parameter Enable communication object "Forced operation" 1-bit has been
selected with the option Yes in
If a forced operation is activated, the device switches to forced operation regardless of the control value and its
parameterized Limitation 1...4.
Telegram value:
66
This communication object is enabled if Automatic operation has been enabled in
level), p. 124.
If automatic operation is enabled, it will be activated after a download, an ETS reset or by an ON telegram on this
communication object.
Automatic mode is switched off if a telegram is received on a "manual communication object".
Manual communication objects are:
During forced operation, automatic mode remains active but operates only within the allowed limits.
If the value 1 is set in the parameter:
Telegram value:
If the value 0 is set in the parameter:
Telegram value:
67
This communication object is enabled if the parameter Enable communication object "Status Automatic" 1-bit has been
selected with the option Yes in
You can parameterize whether the communication object value is updated but not sent, sent on request, or only sent when
changed.
The communication object indicates the status of automatic operation.
Telegram value:
220 2CDC508134D0202 | FCA/S 1.x.x.1
Functionality
Forced operation
Parameter window E, F, G: Fan
0 = No forced operation
1 = Forced operation
Automatic ON/OFF
Fan: Switch speed
Fan: Switch speed x (x = 1, 2 or 3)
Fan: Fan speed up/down
Fan: Limitation x (x = 1, 2, 3 or 4)
0 = Automatic operation OFF
1 = Automatic operation ON
0 = Automatic operation ON
1 = Automatic operation OFF
Status Automatic
Parameter window Status messages
0 = Inactive
1 = Activated
communication object name
Fan E, F, G
(Multi-level), p. 124.
Fan E, F, G
Parameter window E, F, G: Fan (Multi-
Fan E, F, G
(Multi-level), p. 129.
Data type
Flags
1 bit
C, W
DPT 1.003
1 bit
C, W
DPT 1.003
1 bit
C, R, T
DPT 1.003