Commissioning
158 2CDC508134D0202 | FCA/S 1.x.x.1
Function of monitoring
Options:
Monitoring current control values
Monitoring active and inactive control values
This parameter determines the scope of monitoring.
Monitoring current control values: Only the currently selected control value input is monitored
for incoming telegram continuity. After a switchover (via Communication object "Toggle control
value A/B" or Largest value), monitoring restarts.
Monitoring active and inactive control values: Both control value inputs are always monitored
independently of each other. An error is reported if an object's time is exceeded.
Note
The fault is reset if both control values are received within the monitoring time.
Send object value
Options:
No, update only
On change
After request
After a change or request
No, update only: The status is updated but not sent.
On change: The status is sent when a change occurs.
After request: The status is sent when a request occurs.
After a change or request: The status is sent on a change or a request.
Set control value during fault
Options:
No
Yes
This parameter sets the reaction in the event of an error.
Selection of option Yes:
Dependent parameter:
Control value in % [0...100]
Options:
This parameter sets what percentage to use for the control value in the event of an
error.
0...30...100