Manual Operation - ABB i-bus KNX Product Manual

Fan coil actuators fca/s
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

®
ABB i-bus
KNX
Device technology
2.6

Manual operation

Function of manual operation
Manual operation facilitates on-site operation of the device. Manual operation is enabled as standard and
can be switched on and off using the Manual operation button
Switching on manual operation:
Switching off manual operation:
After connection to the KNX, an ETS download or ETS reset, the device is in KNX operation. The LED
is off. All LEDs indicate the current state.
Note
If Manual operation is generally disabled or is disabled via communication object Block manual
operation, the LED
A switchover from KNX operation to the Manual operation mode does not occur.
Note
If manual operation is activated, the current fan speed remains set and can only be operated manually.
Here any limitations, forced operations and programmed dwell times are not considered.
If manual operation is deactivated, the fan sets to a speed to which it would also be set without manual
operation, e.g. via the value of the communication objects. The setting occurs with the parameterized
dwell times.
Press the
button until the yellow LED
Press the
button briefly. The yellow LED
flashes during the button push.
.
lights continuously.
continues to flash for 2 seconds.
FCA/S 1.x.x.1 | 2CDC508134D0202 61