KNX
Commissioning
168 2CDC508134D0202 | FCA/S 1.x.x.1
Restart of staircase time after end
of permanent ON
Options:
No
Yes
No: The lighting switches off if Permanent ON is ended.
Yes: The lighting remains on and the staircase lighting time restarts.
The function of Permanent ON is controlled via the Permanent ON communication object value. If
the communication object receives a telegram with the value 1, the output is switched on regardless
of the value of the communication object Switch and remains switched on until the communication
object Permanent ON has the value 0.
Object value "Disable function Time"
after a download
Options:
Unchanged
0 = enable function Time
1 = Disable function Time
This parameter defines how the function Time should react after a download. With a telegram to the
communication object Disable function Time, the function Time can be disabled.
Unchanged: The function Time can continue unchanged.
Note
The state of the Time function is stored with bus voltage failure and continues unchanged after
bus voltage recovery.
0 = Enable function Time: The Time function is enabled by a telegram with the value 0.
Note
If the staircase lighting is disabled when the function Time is operational, the light will stay at ON
until it is switched to OFF manually.
1 = Disable function Time: The Time function is disabled by a telegram with the value 1.
Note
Enabling is only possible via the communication object Disable function Time.