Device Technology; Fan Coil Actuator Fca/S 1.1.1.2, Pwm, Mdrc; Technical Data - ABB i-bus KNX Product Manual

Fan coil actuators fca/s
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

®
ABB i-bus
KNX

Device technology

2
Device technology
2.1

Fan Coil Actuator FCA/S 1.1.1.2, PWM, MDRC

2.1.1

Technical data

Supply
*The maximum power consumption of the device
results from the following specifications:
Connections
Connection terminals
The device is a modular installation
device (MDRC) in Pro M design. It is
intended for installation in distribution
boards on 35 mm mounting rails. The
assignment of the physical addresses as
well as the parameterization is carried out
with ETS.
Bus voltage
Current consumption, bus
Leakage loss, bus
Leakage loss, device
KNX connection
Relay 16 A
Relay 6 A
Electronic outputs
KNX
Inputs/Outputs
Screw terminal
Ferrules without/with plastic sleeves
TWIN ferrules
Tightening torque
Grid
The device is powered via the ABB
®
i-bus
KNX and requires no additional
auxiliary voltage supply. The device is
ready for operation after connecting the
bus voltage.
21...32 V DC
< 12 mA
Maximum 250 mW
Maximum 3.05 W*
0.25 W
1.0 W
0.6 W
1.2 W
Via bus connection terminal
Via screw terminals
Screw terminal with universal head (PZ 1)
0.2...4 mm² stranded, 2 x (0.2...2.5 mm²)
0.2...6 mm² single core, 2 x (0.2...4 mm²)
Without: 0.25...2.5 mm²
With: 0.25...4 mm²
0.5...2.5 mm²
Contact pin length min. 10 mm
Maximum 0.6 Nm
6.35
FCA/S 1.x.x.1 | 2CDC508134D0202 11