ABB i-bus KNX Product Manual page 149

Fan coil actuators fca/s
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

®
ABB i-bus
KNX
Commissioning
Run-on behavior
Options:
This parameter activates a run-on for the fan. If the fan changes to a lower speed, it remains in the
previous speed for the parameterized run-on time and only then reduces the speed by one level.
If the fan goes through several speed changes, run-on times are executed successively, adding on those
times.
A run-on time of 0 seconds means that run-on is deactivated.
Run-on is executed regardless of where the speed change originates (automatic operation, direct
operation, manual procedure, fan switch off).
Selection of option Yes:
No
Yes
Dependent parameters:
Run-on times speed 3
in s [0...65,535]
0...20...65,535
Options:
Run-on times speed 2
in s [0...65,535]
0...20...65,535
Options:
Run-on times speed 1
in s [0...65,535]
0...20...65,535
Options:
FCA/S 1.x.x.1 | 2CDC508134D0202 147