ABB i-bus KNX Product Manual page 220

Fan coil actuators fca/s
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

®
ABB i-bus
KNX
Commissioning
No.
56
This communication object is enabled if the parameter Enable communication object "Status Fan speed x" 1-byte has been
selected with the option Yes in
You can parameterize whether the communication object value is updated only, or sent on the bus after a change or on
request. It is possible to parameterize whether the actual or required speed is displayed with the status communication
object.
This communication object allows you, for example, to display the fan speed as a figure value.
The following telegram values apply for the 1 byte communication object:
57
This communication object is enabled if the parameter Enable communication object "Status Fan speed x" 1-byte has been
selected with the option Yes in
You can parameterize whether the communication object value is updated but not sent, sent on request, or only sent when
changed.
You can also parameterize whether the status should indicate a current fan speed or a required fan speed. This
communication object allows you to display the fan speed in a visualization or to indicate it on a display.
Telegram value:
58
See communication object 57
59
See communication object 57
60
This communication object is enabled if the run-on behavior has been enabled in
If run-on behavior is enabled, it will be activated after an ETS reset or by an ON telegram on this communication object.
Telegram value:
218 2CDC508134D0202 | FCA/S 1.x.x.1
Functionality
Status Fan speed
Parameter window Status messages
Figure value
Hexadecimal
0
1
2
3
Status Fan speed 1
Parameter window Status messages
0 = Fan speed OFF
1 = Fan speed ON
Status Fan speed 2
Status Fan speed 3
Run-on
0 = Run-on disabled
1 = Run-on enabled
communication object name
Fan E, F, G
(Multi-level), p. 129.
Binary value bit
76543210
00
00000000
01
00000001
02
00000010
03
00000011
Fan E, F, G
(Multi-level), p. 129.
Fan E, F, G
Data type
Flags
1-byte
C, R, T
DPT 5.010
Fan speed
0 (OFF)
Fan speed 1
Fan speed 2
Fan speed 3
1 bit
C, R, T
DPT 1.001
1 bit
C, W
DPT 1.003
Parameter window
Startup/Run-on, p. 145.