Praesideo 3.5 | Installation and User Instructions | 9 | System Configuration
43.4.4 General (PRS-CSR and
PRS-CSRK)
figure 43.24: Configure call station, step 1
table 43. 1 2: General configuration settings (PRS-CSR)
Item
Class
Clear selection after call
Remote call station
supervision
Remote call station
network power
supervision
Remote call station
back-up power
supervision
Call station interface
network power
supervision
Call station interface
back-up power
supervision
Bosch Security Systems | 2011-02
Value
Description
Normal
Sets the priority range of the call station. This is either Normal
Emergency
for 32 to 223 or Emergency for 32 to 255. When Class is
Emergency the call station can make fail-safe calls.
Yes
Selects whether selections that are made on a keypad for a call
No
(zone selection, priority selection, tone selection and message
selection) will be cleared after the call has finished or will be
kept for a next call.
On
Selects whether the remote call station and its connection to
the call station interface will be supervised or not. If set to No, it
Off
is possible to disconnect and remove the remote call station
without generating a fault in the system. This can be
convenient for call stations that would otherwise remain
unattended. Emergency call stations should always be
supervised.
On
When Remote call station network power supervision is On
Off
and the network power connection between the remote call
station interface and the remote call station is failing, a fault
event is generated.
On
When Remote call station back-up power supervision is On
Off
and the external power supply that is connected to the remote
call station is failing, a fault event is generated.
On
When Call station interface network power supervision is On
Off
and the network power connection between the call station
interface and the Praesideo network is failing, a fault event is
generated.
On
When Call station interface back-up power supervision is On
Off
and the external power supply that is connected to the call
station interface is failing, a fault event is generated.
en | 355