Clause / Requirement
6 The quiescent condition
Any kind of system information may be displayed during the
quiescent condition. However, no indications shall be given
which could be confused with indications used in the
voice alarm condition,
fault warning condition,
disablement condition (option with requirements).
Bosch Security Systems | 2011-02
Compliance
Praesideo is compliant.
If the Praesideo system enters the voice alarm condition
each call station will show a red system status LED and the
emergency menu will pop up on the display of the network
controller. In the quiescent condition no red indicators are
used at all and the display of the network controller will
never automatically switch to the emergency menu.
If the Praesideo system enters the fault warning condition
each call station will show a yellow (blinking or on) power/
fault LED and the faults menu will pop up on the display of
the network controller. In the quiescent condition the
power/fault LED of each call station will be green and the
display of the network controller will never automatically
switch to the faults menu.
The disablement condition is not implemented in
Praesideo.