Bosch Praesideo 3.5 Installation And User Instructions Manual page 218

Digital public address and emergency sound system
Table of Contents

Advertisement

2011-02 | Installation and User Instructions | 5 | Call Stations
Note
With the exception of the connection to X1 and
X2, the wiring of all other connectors must be
less than 3 meter in length..
18.2.1 Back-up supply (X4)
The external interface for the back-up supply consists of
a pin header connector with 8 positions (see the PCB for
the pin numbering). The connector provides also two
control inputs. These can be used to receive signals
from other equipment. For example, signals from the
back-up supply that indicate its status such as mains
available, battery OK etc.
table 18. 1 : X4 connector details
Pin
Signal
1
GND
2
GND
3
Back-up supply
4
Back-up supply
5
GND
6
Control input 1
7
GND
8
Control input 2
table 18.2: X4 technical data
Backup voltage:
18 to 56 V(DC)
No fault reporting when > 20 V
Backup current:
max. 2 A
Control input 1 and control input 2
Resistance detection (supervision enabled):
Cable short circuit
< 2.5 kohm
Contact closed
7.5 kohm to12 kohm
Contact open
17.5 kohm to 22 kohm
Cable broken
> 27 kohm
Resistance detection (supervision disabled):
Contact closed
< 12 kohm
Contact open
> 17.5 kohm
Bosch Security Systems | 2011-02
The control inputs can be configured to act on contact
make or on contact break (see section 42.5). It is also
possible to supervise the cables for short-circuits and
open connections (see figure 18.3 and figure 18.4).
Whether a control input is actually supervised or not is
defined in the configuration.
GND
10kΩ
figure 18.3: Supervised control input
GND
figure 18.4: Non-supervised control input
Warning
Do not connect DC or AC signals to the control
inputs, otherwise the input circuit may be
damaged. Only use voltage-free contacts.
en | 218
Control input
10kΩ
Control input