Praesideo 3.5 | Installation and User Instructions | 9 | System Configuration
43.2.6 Control outputs
figure 43.8: Configure network controller, step 6
table 43.5: Control outputs configuration
Item
Output
Mains power fault grace
time
Function
Bosch Security Systems | 2011-02
Value
Description
Unique name for the control output. The output can be enabled and
disabled using the checkbox.
Selects whether control output 5 with the fixed function Fault alarm
0 h (default),
indicator acts immediately on the occurrence of a mains power fault, or
1 h, 2 h,
that activation is suspended and will only happen if the mains power
3 h ...8 h
fault is still present after the configured grace time. All other faults will
result in an immediate activation of this Fault alarm indicator. The
purpose of the grace time is to suspend a warning to an external
service center for systems in areas where short mains failures
frequently happen. The system backup power supply should at least
be able to provide power during the configured grace time. The Fault
alarm buzzer is not delayed in order to give a local warning immediately.
Sets the purpose of the control output. See table 43.6.